Publication detail

AUTOMATIC CONTROL OF NITROGEN OXIDES REDUCTION DURING WASTE COMBUSTION

Zdeněk NĚMEC, Radomil MATOUŠEK, Ladislav BÉBAR, Tomáš PAŘÍZEK

Czech title

Automatické řízení redukce oxidů dusíku při spalování odpadů

English title

AUTOMATIC CONTROL OF NITROGEN OXIDES REDUCTION DURING WASTE COMBUSTION

Type

conference paper

Language

en

Original abstract

The paper summarizes knowledge acquired from analysis of automatic control of municipal solid waste incinerator plant. The analysis is concerned with non-catalytic reduction of nitrogen oxides (NOx) in the combustion products by means of injection of ammonia water solution (NH4OH) into the upper part of boiler hearth. An automatic control is used for ammonia’s dosing. Objective of this control is to keep NOx level in the combustion products below the ecological limit. The base of a standard control is a proportional-integrative (PI) controller. It was discovered during the analysis that for the given process the integrative component isn’t suitable. It is because the ammonia reducing potential is limited.

Czech abstract

Příspěvek shrnuje poznatky, získané z analýzy automatického řízení spalovny pevného komunálního odpadu. Analýza se týká problematiky nekatalytické redukce oxidů dusíku (NOx) ve spalinách pomocí vstřikování vodného roztoku amoniaku (NH4OH) do vrchní části ohniště kotle. Dávkování amoniaku je řízeno automaticky a jeho úlohou je udržení úrovně NOx ve spalinách pod dovoleným ekologickým limitem. Základem klasického řízení je regulátor s proporcionálně integračním (PI) regulátorem. Rozborem bylo zjištěno, že pro daný účel je použití integrační složky nevhodné. Důvodem jsou omezené možnosti redukčního účinku amoniaku.

English abstract

The paper summarizes knowledge acquired from analysis of automatic control of municipal solid waste incinerator plant. The analysis is concerned with non-catalytic reduction of nitrogen oxides (NOx) in the combustion products by means of injection of ammonia water solution (NH4OH) into the upper part of boiler hearth. An automatic control is used for ammonia’s dosing. Objective of this control is to keep NOx level in the combustion products below the ecological limit. The base of a standard control is a proportional-integrative (PI) controller. It was discovered during the analysis that for the given process the integrative component isn’t suitable. It is because the ammonia reducing potential is limited.

Keywords in Czech

Spalování komunálního odpadu, oxidy dusíku (NOx), nekatalytická redukce oxidů dusíku, amoniak, automatické řízení, regulace, omezení nasycením.

Keywords in English

Municipal waste incinerator plant, nitrogen oxides (NOx), non-catalytic reduction of nitrogen oxides, ammonia water solution (NH4OH), and automatic control.

RIV year

2006

Released

27.08.2006

Publisher

Process Engineering Publisher, Praha, Czech republik

Location

Praha, Czech Republic

ISBN

80-86059-45-6

Book

CHISA 2006

Pages count

5

BIBTEX


@inproceedings{BUT20213,
  author="Zdeněk {Němec} and Radomil {Matoušek} and Ladislav {Bébar} and Tomáš {Pařízek},
  title="AUTOMATIC CONTROL OF NITROGEN OXIDES REDUCTION DURING WASTE COMBUSTION",
  booktitle="CHISA 2006",
  year="2006",
  month="August",
  publisher="Process Engineering Publisher, Praha, Czech republik",
  address="Praha, Czech Republic",
  isbn="80-86059-45-6"
}