Detail publikace

Automatické řízení redukce oxidů dusíku při spalování odpadů

Zdeněk NĚMEC, Radomil MATOUŠEK, Ladislav BÉBAR, Tomáš PAŘÍZEK

Český název

Automatické řízení redukce oxidů dusíku při spalování odpadů

Anglický název

AUTOMATIC CONTROL OF NITROGEN OXIDES REDUCTION DURING WASTE COMBUSTION

Typ

článek ve sborníku ve WoS nebo Scopus

Jazyk

en

Originální abstrakt

The paper summarizes knowledge acquired from analysis of automatic control of municipal solid waste incinerator plant. The analysis is concerned with non-catalytic reduction of nitrogen oxides (NOx) in the combustion products by means of injection of ammonia water solution (NH4OH) into the upper part of boiler hearth. An automatic control is used for ammonia’s dosing. Objective of this control is to keep NOx level in the combustion products below the ecological limit. The base of a standard control is a proportional-integrative (PI) controller. It was discovered during the analysis that for the given process the integrative component isn’t suitable. It is because the ammonia reducing potential is limited.

Český abstrakt

Příspěvek shrnuje poznatky, získané z analýzy automatického řízení spalovny pevného komunálního odpadu. Analýza se týká problematiky nekatalytické redukce oxidů dusíku (NOx) ve spalinách pomocí vstřikování vodného roztoku amoniaku (NH4OH) do vrchní části ohniště kotle. Dávkování amoniaku je řízeno automaticky a jeho úlohou je udržení úrovně NOx ve spalinách pod dovoleným ekologickým limitem. Základem klasického řízení je regulátor s proporcionálně integračním (PI) regulátorem. Rozborem bylo zjištěno, že pro daný účel je použití integrační složky nevhodné. Důvodem jsou omezené možnosti redukčního účinku amoniaku.

Anglický abstrakt

The paper summarizes knowledge acquired from analysis of automatic control of municipal solid waste incinerator plant. The analysis is concerned with non-catalytic reduction of nitrogen oxides (NOx) in the combustion products by means of injection of ammonia water solution (NH4OH) into the upper part of boiler hearth. An automatic control is used for ammonia’s dosing. Objective of this control is to keep NOx level in the combustion products below the ecological limit. The base of a standard control is a proportional-integrative (PI) controller. It was discovered during the analysis that for the given process the integrative component isn’t suitable. It is because the ammonia reducing potential is limited.

Klíčová slova česky

Spalování komunálního odpadu, oxidy dusíku (NOx), nekatalytická redukce oxidů dusíku, amoniak, automatické řízení, regulace, omezení nasycením.

Klíčová slova anglicky

Municipal waste incinerator plant, nitrogen oxides (NOx), non-catalytic reduction of nitrogen oxides, ammonia water solution (NH4OH), and automatic control.

Rok RIV

2006

Vydáno

27.08.2006

Nakladatel

Process Engineering Publisher, Praha, Czech republik

Místo

Praha, Czech Republic

ISBN

80-86059-45-6

Kniha

CHISA 2006

Počet stran

5

BIBTEX


@inproceedings{BUT20213,
  author="Zdeněk {Němec} and Radomil {Matoušek} and Ladislav {Bébar} and Tomáš {Pařízek},
  title="AUTOMATIC CONTROL OF NITROGEN OXIDES REDUCTION DURING WASTE COMBUSTION",
  booktitle="CHISA 2006",
  year="2006",
  month="August",
  publisher="Process Engineering Publisher, Praha, Czech republik",
  address="Praha, Czech Republic",
  isbn="80-86059-45-6"
}