Jednostupňový absorpční oběh se skrápěným svazkem hladkých trubek

POSPÍŠIL, J. BALÁŠ, M. CHROBOCZEK, L. FORTELNÝ, Z.

Český název

Jednostupňový absorpční oběh se skrápěným svazkem hladkých trubek

Anglický název

One stage absorption cooling cycle with falling film smooth tube bundles

Typ

článek ve sborníku ve WoS nebo Scopus

Jazyk

en

Originální abstrakt

The one-stage experimental absorption chiller with exactly same design of desorber-condenser and absorberevaporator was build up at the Brno University of Technology in 2008. This experimental absorption unit operates with LiBr H2O working pair. Design of the unit keeps two-cylinder conception, which is common for large-scale absorption units. Heat transfer between the working fluid and the heating/cooling water is realized with utilizing of falling film cooper pipe registers. Cooling capacity of the absorption chiller was designed 6 kW on temperature level 9 C. The contribution introduces the design of the 1 stage experimental absorption unit, building, operation experiences and results of carried out measurements. Measurement was focused on assessment of heat transfer on falling film tube bundles and entire COP evaluation. Four independent pumps enable test the influence of flow rate change in different loops of absorption unit.

Český abstrakt

Jednostupňový experimentální absorpční chaldicí oběh se shodným provedením desorbéru-kondenzátoru a absorbéru-výparníku byl realizován na Vysokém učení technickém v roce 2008. Tento experimntální oběh pracuej s pracovní dvojicí LiBr-H2O. Návrh jednotky vychází z dvouválcové koncepce běžné pro velké absorpční jednotky. Přenos tepla mezi pracovní dvojicí a horkou a chladnou vodou je realizován skrápěnými registry měděnými trubek. Chaldicí výkon jednotky byl projektován 6 kW na teplotní hladině 9 sC. Příspěvek popisuje provedení oběhu, výrobu, provozní zkušenosti a výsledky realizovaných měření. Měření byla zaměřena na sledování přenosu tepal skrápěnými trubkovými svazky a hodnocení clekové efektivnosti zařízení. 4 nezávislá čerpadla umožňili testovat proměnlivý průtok pracovních médiií v různých smyčkách experimentálního zařízení.

Anglický abstrakt

The one-stage experimental absorption chiller with exactly same design of desorber-condenser and absorberevaporator was build up at the Brno University of Technology in 2008. This experimental absorption unit operates with LiBr H2O working pair. Design of the unit keeps two-cylinder conception, which is common for large-scale absorption units. Heat transfer between the working fluid and the heating/cooling water is realized with utilizing of falling film cooper pipe registers. Cooling capacity of the absorption chiller was designed 6 kW on temperature level 9 C. The contribution introduces the design of the 1 stage experimental absorption unit, building, operation experiences and results of carried out measurements. Measurement was focused on assessment of heat transfer on falling film tube bundles and entire COP evaluation. Four independent pumps enable test the influence of flow rate change in different loops of absorption unit.

Klíčová slova česky

absorpční jednotka, skrápění, přestup tepla, pracovní stabilizy, trubkový svazek

Klíčová slova anglicky

absorption unit, falling film, heat transfer, working stability, tube bundle

Rok RIV

2009

Vydáno

30.06.2009

Nakladatel

WSEAS

Místo

Ateny, Řecko

ISBN

978-960-474-093-2

Kniha

Energy Problems and Environmental Engineering - Proceedings

Číslo edice

1

Strany od–do

358–362

Počet stran

5

BIBTEX


@inproceedings{BUT31686,
  author="Jiří {Pospíšil} and Marek {Baláš} and Libor {Chroboczek} and Zdeněk {Fortelný},
  title="One stage absorption cooling cycle with falling film smooth tube bundles",
  booktitle="Energy Problems and Environmental Engineering - Proceedings",
  year="2009",
  month="June",
  pages="358--362",
  publisher="WSEAS",
  address="Ateny, Řecko",
  isbn="978-960-474-093-2"
}